Power in alternating current
In direct current, all the power that flows is put to use. In alternating current with coils or capacitors this is not the case: part of the energy goes back and forth without producing useful work. Telling active, reactive and apparent power apart is key to understanding the electricity bill of any industrial installation.
The three kinds of power
Define the three powers in alternating current (active, reactive, and apparent), state the unit for each ($\text{W}$, $\text{VAr}$, $\text{VA}$), and explain which of…
Define the three powers in alternating current (active, reactive, and apparent), state the unit for each ($\text{W}$, $\text{VAr}$, $\text{VA}$), and explain which of them produces useful work and actually heats resistors.
A workshop consumes active power $P = 3\ \text{kW}$ with apparent power $S = 4\ \text{kVA}$, as shown in the power triangle in the diagram. Calculate the power factor of…
A workshop consumes active power $P = 3\ \text{kW}$ with apparent power $S = 4\ \text{kVA}$, as shown in the power triangle in the diagram. Calculate the power factor of the installation and, applying Pythagoras' theorem to the triangle, the reactive power $Q = \sqrt{S^2 - P^2}$.
The power triangle
A single-phase motor operating at $230\ \text{V}$ draws $10\ \text{A}$ with a power factor of $0{,}8$. a) Calculate the apparent power, active power (…
A single-phase motor operating at $230\ \text{V}$ draws $10\ \text{A}$ with a power factor of $0{,}8$. a) Calculate the apparent power, active power ($P = V \cdot I \cdot \cos \varphi$), and reactive power (with $\sen \varphi$ deduced from the triangle). b) Explain which part of the current measured by the ammeter produces no useful work.
An installation consumes $P = 12\ \text{kW}$ with $\cos \varphi = 0{,}6$. a) Calculate the apparent power $S$ and the reactive power $Q$ (use $\sen \varphi = 0{,}8$ for…
An installation consumes $P = 12\ \text{kW}$ with $\cos \varphi = 0{,}6$. a) Calculate the apparent power $S$ and the reactive power $Q$ (use $\sen \varphi = 0{,}8$ for that angle). b) Calculate the current at $400\ \text{V}$ (equivalent single-phase, $I = \frac{S}{V}$) and compare it with the current that would flow with $\cos \varphi = 1$.
A workshop presents $S = 25\ \text{kVA}$ and $Q = 15\ \text{kVAr}$. a) Calculate the active power by applying Pythagoras' theorem to the power triangle. b) Calculate the…
A workshop presents $S = 25\ \text{kVA}$ and $Q = 15\ \text{kVAr}$. a) Calculate the active power by applying Pythagoras' theorem to the power triangle. b) Calculate the power factor. c) Reason whether the installation would pay a penalty given a limit of $\cos \varphi = 0{,}95$.
The power factor
Explain in your own words what the power factor, $\cos \varphi$, is, what values it can take between a purely resistive load and a highly inductive load, and why…
Explain in your own words what the power factor, $\cos \varphi$, is, what values it can take between a purely resistive load and a highly inductive load, and why electricity companies are interested in it being close to $1$.
A single-phase motor operating at $230\ \text{V}$ draws $10\ \text{A}$ with a power factor of $0{,}8$. Keeping the active power constant, calculate the current it would…
A single-phase motor operating at $230\ \text{V}$ draws $10\ \text{A}$ with a power factor of $0{,}8$. Keeping the active power constant, calculate the current it would draw if its power factor were $1$, and reason what practical consequences the current reduction brings (cable cross-sectional area, heating, voltage drop).
Two workshops consume the same active power of $20\ \text{kW}$ at $400\ \text{V}$ (equivalent single-phase), but one operates with $\cos \varphi = 1$ and the other with…
Two workshops consume the same active power of $20\ \text{kW}$ at $400\ \text{V}$ (equivalent single-phase), but one operates with $\cos \varphi = 1$ and the other with $\cos \varphi = 0{,}6$. a) Calculate the current drawn by each and the ratio between them. b) Calculate the Joule losses in a $1\ \Omega$ line for each case ($P_p = R \cdot I^2$) and express them as a percentage of the useful power. c) Draw a conclusion regarding transmission efficiency at a low power factor.
Compensation with capacitors
Explain how capacitors compensate for the reactive energy of inductors: what energy exchange takes place between them in each half-cycle and why the capacitor bank is…
Explain how capacitors compensate for the reactive energy of inductors: what energy exchange takes place between them in each half-cycle and why the capacitor bank is connected in parallel with the installation rather than in series.
An industrial unit has $P = 40\ \text{kW}$ and $\cos \varphi = 0{,}8$, and wants to increase it to $0{,}98$. a) Calculate the current reactive power (with…
An industrial unit has $P = 40\ \text{kW}$ and $\cos \varphi = 0{,}8$, and wants to increase it to $0{,}98$. a) Calculate the current reactive power (with $\sen \varphi = 0{,}6$) and the permissible reactive power after the upgrade (with $\sen \varphi \approx 0{,}2$). b) Obtain by subtraction the required rating of the capacitor bank. c) Comment on why the bank is installed with automatic steps.
A factory has a power factor of $0{,}7$ and consumes $50\ \text{kW}$ of active power. The supplier penalises consumptions with $\cos \varphi < 0{,}95$. a) Calculate the…
A factory has a power factor of $0{,}7$ and consumes $50\ \text{kW}$ of active power. The supplier penalises consumptions with $\cos \varphi < 0{,}95$. a) Calculate the current apparent power and reactive power. b) Calculate the reactive power remaining with $\cos \varphi = 0{,}95$ (you may use $\sen \varphi \approx 0{,}31$) and, by subtraction, the capacitive reactive power that the capacitor bank must supply. c) Comment on why correction does not reduce the active energy bill but does reduce other charges.